Use the rotary dial on the front of the unit to set the light level at which the circuit should activate.
Install the photo-electric cell outdoors. It must be positioned away from the lights it controls to avoid "cycling" (turning off because it sees its own light). Wiring the Terminals: Terminals 1 & 2: Connect to the 230V AC power supply.
Test for a short circuit in the wiring between terminals 6 and 7. Check the Green LED for power supply. Merlin Gerin Multi 9 Ic 2000 P Manual
The IC 2000 P is an analog twilight switch that uses a remote photo-electric cell (sensor) to detect outdoor light intensity. Multi 9 Operating Voltage: 230V AC (+10% / -15%) at 50/60 Hz Breaking Capacity: 16A at 250V AC (cos phi = 1) Brightness Range: Adjustable from 2 to 2000 Lux Mounting: 35mm DIN rail Protection Rating: IP20 (Device), IP54 to IP65 (Sensor) Installation Guidelines
Indicates that the brightness detected by the sensor is below the set threshold (the output relay is active). Troubleshooting Common Issues Lights stay on during the day: Check if the sensor is covered by debris, snow, or dirt. Verify the Lux dial isn't set too high (near 2000 Lux). Use the rotary dial on the front of
Approx. 20 to 80 seconds.The unit must sense a consistent light level for this duration before switching states. 3. LED Indicators Green LED: Indicates that the device is powered on.
Connect the two wires leading to the external photo-electric sensor. There is no polarity to observe for the sensor wires. Programming and Calibration Wiring the Terminals: Terminals 1 & 2: Connect
Lights will turn on only when it is quite dark (approx. 2-50 Lux).